Translations:Sensors Modbus Management/16/en
| 110 || holding || RW|| 96 || baud rate / 100 || RS-485 port speed, divided by 100. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(Configure RS-485 communication parameters for Wiren Board Modbus devices)
|colspan="5"|all
| rowspan="3" |>3.1.0
|-
| 111 || holding || RW|| 0 || || configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even)
|colspan="5"|all
|-
| 112 || holding || RW|| 2 || || number of stop bits of RS-485 port. Valid values: 1, 2
|colspan="5"|all
|-
| 120 (0x78) || holding || RW|| 0 || non-0 || writing to the register causes the module to restart without saving state
|colspan="5"|all
|
|-
| 121 (0x79) || input || R || - || mV || current supply voltage of the module
|colspan="5"|all
|
|-
| 128 (0x80) || holding || RW|| 1 || || Modbus device address
|colspan="5"|all
|
|-
| 129 (0x81) || holding || RW|| 0 || 0 or 1 || Go to bootloader mode
|colspan="5"|all || 4.5.0
|-
| 200-206 || input || R || see Device signature || || signature
|colspan="5"|all
|
|-
| 220-241 || input || R | | | | _date__ _time__|| firmware build date
|colspan="5"|all
|
|-
|245
|holding
|RW
|0
|°C × 100 (signed)
|Self-heating temperature compensation for temperature and humidity sensor (value is subtracted from measured temperature)
| +
| -
| -
| -
| +
|4.2
|-
| 250-269 || input || R | | | / string, null-terminated || firmware version
|colspan="5"|all
|
|-
| 270-271 || input || R|| || 32-bit unsigned int || unique identifier (S/N)
|colspan="5"|all
|
|-
|280||input||R|| ||
||Maximum value of motion sensor with ADC
| -
| -
| -
| -
| +
|
|-
|281||input||R|| ||
||Value of the motion sensor with ADC
| -
| -
| -
| -
| +
|
|-
|282||holding||RW||10||s
||The width of the time window for calculating the maximum average value of the motion sensor (from 1 to 60 seconds)
| -
| -
| -
| -
| +
|
|-
|283||input||R|| ||
||Current average value of movement in conventional units
| -
| -
| -
| -
| +
|
|-