WBIO-DO-R10A-8 Relay Module/en: различия между версиями
(Новая страница: «{| class="wikitable" !Parameter !Value |- |Number of outputs |8 |- |Output type |mechanical relay |- |Contact configuration |SPST, normally open states:») |
(Новая страница: «* off. * C is closed and NO |- |Maximum switching voltage, alternating current |250 V |- |Maximum switching voltage, direct current |30 Volts |- |Maximum switchin…») |
||
Строка 31: | Строка 31: | ||
states: | states: | ||
* | * off. | ||
* | * C is closed and NO | ||
|- | |- | ||
| | |Maximum switching voltage, alternating current | ||
|250 | |250 V | ||
|- | |- | ||
| | |Maximum switching voltage, direct current | ||
|30 | |30 Volts | ||
|- | |- | ||
| | |Maximum switching current, per channel (*) | ||
|7 | |7 A | ||
|- | |- | ||
| | |The channel resistance in the open state | ||
|< 100 | |< 100 megohms | ||
|- | |- | ||
| | |Voltage isolation between the controller and the output | ||
|1500 | |1500 V (RMS.) | ||
|- | |- | ||
| | |Lifetime: number of switches | ||
for load 10 A 230 V AC, cos φ = 1 | |||
|100 000 | |100 000 | ||
|- | |- | ||
| | |Module type | ||
|"O" (non-inverted address scheme) | |"O" (non-inverted address scheme) | ||
|- | |- | ||
| | |Maximum power consumption | ||
|1 | |1 W | ||
|- | |- | ||
| | |Width, DIN units | ||
|3 | |3 | ||
|- | |- | ||
| | |Size | ||
|53,3x90,2x57,5 | |53,3x90,2x57,5 mm | ||
|} | |} | ||
Версия 17:26, 15 июля 2019
Purpose
Control of lighting, motors, contactors.
Technical specifications
Contains 8 HF32F-G relays (Datasheet) with SPST contacts configuration (two contacts per relay: NO/COM) switching the corresponding 8 outputs. The outputs are output to screw clamps designed for a maximum current of 20 A.
Permissible current up to 7A per channel. The module has protection against sparking of the contacts.
Our detailed article in russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/
Parameter | Value |
---|---|
Number of outputs | 8 |
Output type | mechanical relay |
Contact configuration | SPST, normally open
states:
|
Maximum switching voltage, alternating current | 250 V |
Maximum switching voltage, direct current | 30 Volts |
Maximum switching current, per channel (*) | 7 A |
The channel resistance in the open state | < 100 megohms |
Voltage isolation between the controller and the output | 1500 V (RMS.) |
Lifetime: number of switches
for load 10 A 230 V AC, cos φ = 1 |
100 000 |
Module type | "O" (non-inverted address scheme) |
Maximum power consumption | 1 W |
Width, DIN units | 3 |
Size | 53,3x90,2x57,5 mm |
*) Максимальный коммутируемый ток указан для резистивной нагрузки 230 В переменного тока.
Клеммники и сечение проводов | |
---|---|
Рекомендуемое сечение провода с НШВИ, мм2 | 2,5 |
Длина стандартной втулки НШВИ, мм | 8 |
Момент затяжки винтов, Н∙м | 0,5 |
Подключение к контроллеру
Смотрите раздел Активирование в веб-интерфейсе контроллера. В поле "Module type" следует выбрать устройство WBIO-DO-RxA-8: 8 Channel Relay I/O module. В веб-интерфейсе реле будут представлены контролами EXTx_R3A1 — EXTx_R3A8 устройства Discrete I/O. Соответствующие MQTT-топики: /devices/wb-gpio/controls/EXTx_R3Ay.
Подключение нагрузки
Реле подключаются в разрыв фазы.
Изображения и чертежи устройства
По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-AO-10V-8.
Corel Draw 2018: WBIO-AO-10V-8.cdr.zip
Corel Draw PDF: WBIO-AO-10V-8.cdr.pdf
Autocad 2013 DXF: WBIO-AO-10V-8.dxf.zip
Autocad PDF: WBIO-AO-10V-8.pdf